N2XSY, NA2XSY

Energy Cables with XLPE Insulation and PVC Sheath
Standards:

HRN HD 620 S2 Part 10C
IEC 60 502-2
DIN VDE 0276T 620

Structure of the Cable

  1. Conductor: Aluminum or copper stranded wire
  2. Conductor Screen: Semiconductive layer on the conductor
  3. Insulation: XLPE
  4. Insulation Screen: Semiconductive layer on the insulation
  5. Separator: Semiconductive tape
  6. Electrical Protection/Screen: Copper wire (single-core), copper tape (three-core)
  7. Separator: Polyester tape
  8. Filling: PVC
  9. Outer Sheath: PVC

Field of Application
For installation underground, in ducts, or on supports where mechanical damage or mechanical tensile stress is not expected. Used as a distribution cable in urban and rural networks and as a connection cable for industrial plants.

Technical Data

  • Old Designation: XHP 48, XHP 48-A
  • Rated Voltage: 6/10/12 kV, 12/20/24 kV
  • Highest Voltage: 12 kV, 24 kV
  • Test Voltage: 21 kV, 35 kV
  • Standards: IEC 60 502-2; HRN HD 620 S2 Part 10C; DIN VDE 0276T 620

Related products

XHEh 91, XHEh 91-A

Energy cables with XLPE insulation, additional electrical protection, and external semiconductive sheath

HRN HD 620 S1
IEC 60 502-2

N2XS(F)2Y, NA2XS(F)2Y

Energy cables with XLPE insulation and PE sheath with longitudinal water-resistant electrical protection

HRN HD 620 S2 Part 10C

IEC 60 502-2

DIN VDE 0276T 620

XLPE-Ay Tip-23, XLPE-Ay Tip-27

Isolated Medium Voltage Overhead Power Cables

Standard: SFS 5791

N2XSEYRY, NA2XSEYRY

Energy cables with XLPE insulation and PVC sheath, reinforced with round steel wires
HRN HD 620 S1 Part 6 A-2
IEC 60 502-2


ISO 9001

ISO 14001

ISO 45001

ISO 50001

VDE