Halogen-Free Fire-Resistant Energy and Signal Cable
Insulated with G10 rubber and sheathed with thermoplastic LSOH material.
CEI 20-45
Structure of the Cable
- Conductor: Fine-stranded copper wire, class 5, CEI EN 60228
- Thermal Barrier: Mica tape
- Insulation: Halogen-free rubber mixture LSOH, TYPE G10, CEI 20-11, CEI EN 50363
- Filler: Non-hygroscopic halogen-free material
- Sheath: Thermoplastic halogen-free LSOH material, type M1, CEI 20-11, CEI EN 50363
- Sheath Color: Blue, Ral 5015 or other upon request
Insulation Colors:
- Single-core: Black
- Double-core: Blue-Brown
- Three-core: Brown-Black-Grey or Green/Yellow-Blue-Brown
- Four-core: Blue-Brown-Black-Grey or Green/Yellow-Brown-Black-Grey
- Five-core: Green/Yellow-Blue-Brown-Black-Grey
- Seven-core and multi-core: Black with numbers with Green/Yellow
Field of Application
The cable is installed in systems with exceptional tasks of maintaining the function and continuity of operation of devices and equipment in fire conditions. It is suitable for high-security buildings to protect human lives and significant material values: hospitals, schools, theaters, cinemas, sports halls, industrial complexes, power plants, underground railways, alarm systems, emergency power supply systems, etc.
Technical Data
- Nominal Voltage: 0.6/1 kV
- Test Voltage: 4 kV
- Standards: CEI 20-45
- Max Operating Temperature of Conductor: 90° C
- Max Temperature in Short Circuit: +250° C, up to 5 seconds
- Flammability Testing: CEI 20-22 II, IEC 60332-1, IEC 60332-3C, CEI EN 50265-1-2, EN 50200, IEC 60331
- Testing for Corrosion and Halogens: CEI EN 50267-2-1
- Smoke Emission Testing: CEI EN 50268-2
Marking on Sheath:
FG10OM1 E90 5 x 16 mm² CEI 20-45 CEI 20-22 III DIN 4102-12 ELKA HR
Key Properties and Testing
- Does not contain halogen elements or their compounds: IEC 60754-1, EN 50267-1, -2, -1
- Flame retardant and self-extinguishing: IEC 60332-1
- Increased resistance to flame spread along the route, vertical bundle: IEC 60332-3C
- Does not emit toxic, corrosive, and conductive gases during burning: EN 50267-2-2/3, IEC 60754-2
- Does not produce dense smoke during burning, visibility > 60%: IEC 61034
- Preservation of insulation properties without short circuit in fire conditions for at least 180 minutes (insulation integrity): IEC 60331
- Preservation of function and continuity of system operation in fire conditions for at least 90 minutes (E90): DIN 4102-12