Telecommunication, armored, flame-retardant halogen-free cable with individual and common screen for 60 V, 250 V, and 0.6/1 kV
Standards:
IEC 60092-350
IEC 60092-353
IEC 60092-376
Cable Structure:
- Conductor: Tinned copper wire class 2, IEC 60228 (see table)
- Separator: Mica tape
- Insulation: XLPE, according to IEC 60092-351
- Individual pair screen: Metalized polyester tape with drainage wire
- Separator: As required
- Common screen: Metalized polyester tape with drainage wire
- Filler and inner sheath: Polyolefin-based mixture
- Armoring: Braid made of tinned copper wires (minimum density 90%)
- Sheath: Polyolefin, type SHF 1 according to IEC 60092-359 (SHF 2 on request)
Colors:
- Sheath color: Gray or orange
- Insulation colors: White or black, numbered: 1, 2…n
Pair construction: 1-2; 3-4; 5-6
Marking on the sheath:
- ELKA CS ATOX-MARIN TBX(Z)OZO-HFVO nxSmm² 60 V/250 V (or 0.6/1 kV)
- IEC 60092-376, IEC 60332-3A, IEC 60331
- or (IEC 60092-353, IEC 60332-3A, IEC 60331)
Field of Application:
Technical Data:
- Nominal voltage: 60 V, 250 V, 0.6/1 kV
- Test voltage: 1500 V, 1500 V, 3.5 kV
- Standards: IEC 60092-350, IEC 60092-353, IEC 60092-376
- Max operating temperature of conductor: 90 °C
- Flame testing: IEC 60331, IEC 60332-1, IEC 60332-3A
- Corrosion testing: IEC 60754-1
- Smoke density testing: IEC 61034