Insulated medium voltage overhead power cables
SFS 5791
keyboard_arrow_downCable structure
1-conductor: rope of aluminium alloy, AlMgSi
2-insulation: XLPE, resistant to weathering factors
2-insulation: XLPE, resistant to weathering factors
keyboard_arrow_downApplication
For overhead insulated distributive networks of nominal voltages 6/10 kV and 12/20 kV. Especially suitable solution for construction of overhead networks in forest areas due to reduced width of cutting through forest and lower cost of construction and maintenance as related to the networks with bare conductors.
keyboard_arrow_downTechnical data
nominal voltage: 12/20 kV
max network voltage: 24 kV
test voltage: 24 kV
standardi: SFS 5791
max network voltage: 24 kV
test voltage: 24 kV
standardi: SFS 5791
keyboard_arrow_downCross-sections (table)
XLPE-Ay Tip-23, XLPE-Ay Tip-27
Cross Section | Min no of wires | Conductor dia | Insulation thickness/TIP 23 | Ins. thick./TIP 27 | Diameter over insulation/TIP 23 | Dia over insu/TIP 27 | Insul. conductor weight/TIP23 | Insul. conductor weight/TIP27 |
---|---|---|---|---|---|---|---|---|
(mm2) | (n) | (mm) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (kg/km) |
35 | 7 | 5,5 | 6,9 | 2,3 | 2,7 | 11,9 | 12,7 | 200 |
50 | 7 | 5,5 | 8,0 | 2,3 | 2,7 | 13,9 | 13,8 | 245 |
70 | 7 | 5,5 | 9,6 | 2,3 | 2,7 | 14,7 | 15,4 | 325 |
95 | 7 | 5,5 | 11,3 | 2,3 | 2,7 | 16,3 | 17,1 | 410 |
120 | 19 | 5,5 | 12,7 | 2,3 | 2,7 | 17,7 | 18,5 | 490 |
150 | 34 | 5,5 | 14,1 | 2,3 | 2,7 | 19,1 | 19,9 | 580 |
185 | 34 | 5,5 | 15,7 | 2,3 | 2,7 | 20,7 | 21,5 | 700 |