PVC insulated and sheathed flat webbed wiring cable

HRN N. C3. 230

The wiring cable PP/R consists of a PVC insulated copper conductor. The cores are laid paralelly and protected by a PVC sheath, forming a bridge between the cores, this making possible teporary fixing of the cables. The cable with protective core (green/yellow) is coded PP/R-Y.

COLOUR OF INSULATION

No of cores | Cable with protective conductor (coded Y) | Cable without protective conductor
2 | - | black-blue
3 | green/yellow-black-blue | black-blue-brown
The conductor type PP/R is intended for wiring in dry conditions for permament laying in plaster or under plaster.
coded acc. to HRN HD: PP/R HRN N. C3. 230
coded acc. to VDE: NYIFY VDE 0250
nominal voltage: 380 V
test voltage: 2000 V
PP/R (NYIFY)
Konstruk. voda Konstruk. vodiča Debljina izolacije Debljina plašta Vanjski promjer Najmanji otpor izolacije pri 70°C Težina kabela Kolut Dužina
Construction of cable Constr. of conductor. Insul. Thickness Sheath thickness Overall diam. Min. insulation resistance @70°C Total weight Coil Length
(mm2) (nxmm) (mm) (mm) (mm) (MOhm/km) (kg/mm) (tip) (m)
2 x 1.50 1 x 1,36 0,6 0,6 4,1 x 11,9 0,010 70 200 100
2 x 2,5 1 x 1,75 0,7 0,7 4,9 x 13,6 0,009 103 315 100
2 x 4 1 x 2,23 0,8 0,7 5,6 x 15,2 0,008 140 315 100
3 x 1,50 1 x 1,36 0,6 0,6 4,1 x 15,8 0,010 102 315 100
3 x 2,5 1 x 1,75 0,7 0,7 4,9 x 18,3 0,009 152 315 100
3 x 4 1 x 2,23 0,8 0,7 5,6 x 20,6 0,008 203 315 100