PVC insulated small-gauge wiring cable

227 IEC 02, IEC 60227-3

1-conductor: untinned small-gauge copper wire strand
2-insulation: PVC compund

Colours of insulation according to standard: black, light-blue, brown and green/yellow.
On requestm due copper conductor may be tinned and thus coded "P/FK".
Wiring cables type "P/F" are intended for usage in dry conditions where extra flexibility is needed. For housing apartments, the wiring is laid in tubes.
coded acc. to HRN HD: H07V-K, HRN HD 21.3 S3
coded acc. to IEC:227 IEC 02,IEC 60227-3
nominal voltage: 450/750 V
test voltage: 2500 V

H07V-K, P/F>
Nazivni presjek Konstrukcija vodiča Debljina izolacije Vanjski promjer Težina kabela Duljina Kolut
Cores x Cross-section Cond. Diam. Insul. Thickness Outer Diam. Cable weight Length Coil
(mm2) (nxmm) (mm) (mm) (kg/mm) (m) (tip)
0,5 15x0,20 0,6 2,3 9 300 200
0,75 22x0,20 0,6 2,4 12 300 200
1,0 30x0,20 0,6 2,6 14 300 200
1,5 28x0,25 0,7 3,1 21 100 125
2,5 46x0,25 0,8 3,7 31 100 125
4 51x0,30 0,8 4,2 45 100 125
6 74x0,30 0,8 4,7 63 100 125
10 7x11x0,40 1,0 6,1 114 100 200
16 7x17x0,40 1,0 7,2 170 100 200
25 7x26x0,40 1,2 8,6 255 100 200
35 19x14x0,40 1,2 10,0 354 1000 B-8
50 19x19x0,40 1,4 11,8 482 1000 B-9
70 19x17x0,50 1,4 13,3 671 1000 B-10
95 19x23x0,50 1,6 15,4 897 1000 B-10
120 19x29x0,50 1,6 16,9 1132 1000 B-12
150 37x19x0,50 1,8 19,3 1390 1000 B-12
185 36x24x0,50 2,0 21,1 1721 1000 B-12
240 47x30x0,50 2,2 24,0 2235 1000 B-14