Power cables with XLPE insulation and PVC sheath
HRN HD 620 S2 Part 10C
IEC 60 502-2
DIN VDE 0276T 620
keyboard_arrow_downCable structure
1-conductor: Al ili Cu rope, compacted
2-conductor screen: semi conductive layer over conductor
3-insulation: XLPE
4-insulation screen: semi conductive layer over insulation
5-separator: semi conductive tape
6-electric protection/screen: of Cu wire (single-core), of Cu tape (three-core)
7-separator: polyester tape
8-filler: PVC
9-external sheath: PVC
2-conductor screen: semi conductive layer over conductor
3-insulation: XLPE
4-insulation screen: semi conductive layer over insulation
5-separator: semi conductive tape
6-electric protection/screen: of Cu wire (single-core), of Cu tape (three-core)
7-separator: polyester tape
8-filler: PVC
9-external sheath: PVC
keyboard_arrow_downApplication
In earth, ducts, on cable trays, where no mechanical damages or mechanical tensile strains are expected. As distributive cable in urban and rural networks. As connecting cable for industrial plants.
keyboard_arrow_downTechnical data
former code:XHP 48, XHP 48-A
nominal voltage: 6/10/12 kV, 12/20/24 kV
max network voltage: 12kV, 24kV
test voltage: 21 kV, 35 kV
standardi: IEC 60 502-2; HRN HD 620 S2 Part 10C; DIN VDE 0276T 620
nominal voltage: 6/10/12 kV, 12/20/24 kV
max network voltage: 12kV, 24kV
test voltage: 21 kV, 35 kV
standardi: IEC 60 502-2; HRN HD 620 S2 Part 10C; DIN VDE 0276T 620
keyboard_arrow_downCross-sections (table)
N2XSY, NA2XSY 6/10/12 kV, single-core
N2XSY, NA2XSY 6/10/12 kV, three-core
Cross-section | Conductor diameter | Insul. thickness | Diameter over insul. | Sheath thickness | Cable diam. | Cable weight Cu | Cable weight Al | Min bending radius |
---|---|---|---|---|---|---|---|---|
(nxmm2/mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (kg/km) | (mm) |
1x35/16 | 7,2 | 3,4 | 16,2 | 2,5 | 23 | 890 | 660 | 340 |
1x50/16 | 8,3 | 3,4 | 17,3 | 2,5 | 25 | 1020 | 750 | 370 |
1x70/16 | 10,3 | 3,4 | 19,3 | 2,5 | 27 | 1210 | 850 | 400 |
1x95/16 | 11,3 | 3,4 | 20,3 | 2,5 | 28 | 1520 | 950 | 420 |
1x120/16 | 12,7 | 3,4 | 21,7 | 2,5 | 30 | 1770 | 1060 | 450 |
1x150/25 | 14,1 | 3,4 | 23,1 | 2,5 | 32 | 2150 | 1250 | 480 |
1x185/25 | 15,7 | 3,4 | 24,7 | 2,5 | 35 | 2570 | 1430 | 520 |
1x240/25 | 18,0 | 3,4 | 27,2 | 2,5 | 37 | 3100 | 1600 | 550 |
1x300/25 | 20,0 | 3,4 | 29,2 | 2,5 | 39 | 3750 | 1850 | 580 |
1x400/35 | 23,8 | 3,4 | 33,2 | 2,5 | 41 | 4750 | 2300 | 610 |
1x500/35 | 26,7 | 3,4 | 36,1 | 2,5 | 44 | 5880 | 2550 | 660 |
Cross-section | Conductor diameter | Insul. thickness | Diameter over insul. | Sheath thickness | Cable diam. | Cable weight Cu | Cable weight Al | Min bending radius |
---|---|---|---|---|---|---|---|---|
(nxmm2/mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (kg/km) | (mm) |
3x35/16 | 7,2 | 3,4 | 16,2 | 2,5 | 46 | 3200 | 2550 | 550 |
3x50/16 | 8,3 | 3,4 | 17,3 | 2,5 | 48 | 3750 | 2800 | 570 |
3x70/16 | 10,3 | 3,4 | 19,3 | 2,5 | 51 | 4500 | 3200 | 610 |
3x95/16 | 11,3 | 3,4 | 20,3 | 2,6 | 55 | 5500 | 3750 | 660 |
3x120/16 | 12,7 | 3,4 | 21,7 | 2,7 | 60 | 6800 | 4600 | 720 |
3x150/25 | 14,1 | 3,4 | 23,1 | 2,8 | 64 | 8000 | 5200 | 760 |
3x185/25 | 15,7 | 3,4 | 24,7 | 2,9 | 66 | 9200 | 5750 | 790 |
3x240/25 | 18,0 | 3,4 | 27,2 | 3,1 | 71 | 10700 | 6200 | 850 |
3x300/25 | 20,0 | 3,4 | 29,2 | 3,2 | 76 | 13100 | 7500 | 910 |