Power cables with XLPE insulation and PVC sheath, armoured with round steel wires
HRN HD 620 S1 Part 6 A-2
IEC 60 502-2

1-conductor: Al or Cu rope, compacted
2-conductor screen: semi-conductive layer over conductor
3-insulation: XLPE
4-insulation screen: semi-conductive layer over insulation
5-electric protection/screen: of Cu tape
6-inner sheath: PVC
7-armour: galvanized steel round wires and coil of galvanized steel tape
8-external sheath: PVC
In earth, ducts, on cable trays, where no mechanical damages or mechanical tensile strains are expected. As distributive cable in urban and rural networks. As connecting cable for industrial plants
former code:XHP 84, XHP 84-A
type coded acc. to HRN HD:E-2XHCEYRY, E-A2XHCEYRY
type coded acc. to DIN VDE:N2XSEYRY, NA2XSEYRY

nominal voltage: 6/10/12 kV
max network voltage: 12kV
test voltage: 21 kV
standardi: IEC 60 502-2; HRN HD 620 S1 Part 6A-2
N2XSEYRY, NA2XSEYRY 6/10/12 kV
Cross-section Conductor diameter Insul. thickness Diameter over insul. Sheath thickness Cable diam. Cable weight Cu Cable weight Al Min bending radius
(nxmm2/mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (mm)
3x35/16 7,2 3,4 16,2 2,6 52 5400 4750 620
3x50/16 8,3 3,4 17,3 2,7 54 6000 5050 650
3x70/16 10,3 3,4 19,3 2,8 57 6900 5600 680
3x95/16 11,3 3,4 20,3 2,9 61 8100 6400 730
3x120/16 12,7 3,4 21,7 3,0 66 9700 7500 790
3x150/25 14,1 3,4 23,1 3,2 71 11600 8800 850
3x185/25 15,7 3,4 24,7 3,4 73 12900 9500 870
3x240/25 18,0 3,4 27,2 3,6 78 14700 10200 930
3x300/25 20,0 3,4 29,2 3,8 83 17400 11800 1000