Flame-retardant power cables with flame-retardant XLPE insulation and flame-retardant polyolefin sheath, halogen-free

IEC 60 502-1 (Cu/XLPE/PO-HFRR)

DIN VDE 0266

*old code:  XO 00-HFTG

1-conductor: Cu rope
2-insulation: halogen-free flame-retardant XLPE compound
3-filling: extruded flame-retardant elastomer or plastomer compound or wrapped flame-retardant thermoplastic tapes
4-sheath: flame-retardant halogen-free polyolefin
In ducts, on support brackets, in dry and wet conditions, where no increased mechanical strains are expected.
For power and signal distribution in industrial plants, public purpose and other facilities where fire prevention safety measures are requested, for elevated electricity and thermic strains (operating temperature of the conductor up to 90°C).
nominal voltage:1 kV
test voltage: 4 kV
standards: DIN VDE 0266, IEC 60 502-1
inflammability test acc. to: IEC 332-3, kat. A
acidity of gasses test acc. to: IEC 360754-2
N2XH
cross-section (n x mm2) insul. thickness (mm) sheath thickness (mm) overall diam (mm) cable weight (kg/km) length (m) drum (type)
2x16 0,7 1,8 17,6 625 1000 BD-12
2x25 0,9 1,8 21,0 925 1000 BD-12
2x35 0,9 1,8 23,2 1190 1000 BD-14
3x16 0,7 1,8 18,6 780 1000 BD-12
3x25 0,9 1,8 22,2 1070 1000 BD-14
3x35 0,9 1,8 24,6 1535 1000 BD-14
4x16 0,7 1,8 20,4 980 1000 BD-12
4x25 0,9 1,8 24,3 1490 1000 BD-14
4x35 0,9 1,9 28,2 2015 1000 BD-16
4x50 1,0 1,9 28,2 2165 1000 BD-16
4x70 1,1 2,0 32,2 3030 500 BD-14
4x95 1,1 2,1 36,4 3965 500 BD-14
4x120 1,2 2,2 39,1 5060 500 BD-16
4x150 1,4 2,4 45,1 6115 500 BD-18
4x185 1,6 2,5 49,4 8005 500 BD-20
4x240 1,7 2,7 54,0 9950 500 BD-20
4x300 1,8 2,9 59,4 12865 500 BD-20