Special medium voltage mining cables
ISE G-001
VDE 0250/Teil 813
keyboard_arrow_downCable structure
1-phase conductor: tinned copper fine-wired rope
2-control conductor: tinned copper fine-wired rope
3-protective conductor: tinned copper fine-wired rope
4-semi-conductive layer: rubber compound at ethylene-propylene elastomere base (EPDM)
5-insulation phase conductor: rubber compound at ethylene-propylene elastomere base (EPDM)
6-semi-conductive layer of phase conductor: rubber compound at ethylene-propylene elastomere base (EPDM)
7-electric protection: braiding of tinned copper wire
8-insulation control conductor: rubber compound at ethylene-propylene elastomere base (EPDM)
9-semi-conductive layer of protective conductor: rubber compound at ethylene-propylene elastomere base (EPDM)
10-separator: semi-conductive textile tape and polyester tape
11-inner sheath: rubber compound at natural and styrene-butadiene elastomere base (NR+SBR)
12-plašt: rubber compound at polychloroprene elastomere base (PCP)
Sheath colour: red
2-control conductor: tinned copper fine-wired rope
3-protective conductor: tinned copper fine-wired rope
4-semi-conductive layer: rubber compound at ethylene-propylene elastomere base (EPDM)
5-insulation phase conductor: rubber compound at ethylene-propylene elastomere base (EPDM)
6-semi-conductive layer of phase conductor: rubber compound at ethylene-propylene elastomere base (EPDM)
7-electric protection: braiding of tinned copper wire
8-insulation control conductor: rubber compound at ethylene-propylene elastomere base (EPDM)
9-semi-conductive layer of protective conductor: rubber compound at ethylene-propylene elastomere base (EPDM)
10-separator: semi-conductive textile tape and polyester tape
11-inner sheath: rubber compound at natural and styrene-butadiene elastomere base (NR+SBR)
12-plašt: rubber compound at polychloroprene elastomere base (PCP)
Sheath colour: red
keyboard_arrow_downApplication
Cables are intended for operation in extremely heavy conditions in surface pit mines, shipyards, quarries and industry. They are specially suitable for supply of heavy excavators, cranes, truck transporters, loading bridges and other machines, with possible continuous movement of cable.
keyboard_arrow_downTechnical data
nominal voltage: 3,6/6 kV
test voltage: 11 kV
standards: ISE G-001; VDE 0250/Teil 813
Permissible conductor temperature: 90°C
Short circuit temperature: 250°C
SHEATH INSCRIPTION: EpN 78/53 3x35+2x16+1x10 mm2 3,6/6 kV ELKA HR year of production
test voltage: 11 kV
standards: ISE G-001; VDE 0250/Teil 813
Permissible conductor temperature: 90°C
Short circuit temperature: 250°C
SHEATH INSCRIPTION: EpN 78/53 3x35+2x16+1x10 mm2 3,6/6 kV ELKA HR year of production
keyboard_arrow_downCross-sections (table)
EpN 78/53
n - broj faznih vodiča - number of phase conductors
n1 - broj upravljačkih vodiča - number of control conductors
n2 - broj zaštitnih vodiča - number of protective conductors
S - presjek faznog vodiča - phase conductor cross-section
S1 - presjek upravljačkog vodiča - control conductor cross-section
S2 - presjek zaštitnog vodiča - protective conductor cross-section
Konstrukcija | Promjer faznog vodiča | Promjer zaštitnog vodiča | Promjer upravljačkog vodiča | Debljina izolacije | Debljina plašta | Vanjski promjer | Težina kabela | Dužina | Bubanj |
---|---|---|---|---|---|---|---|---|---|
Construction | Phase conductor diameter | Protective conductor diameter | Control conductor diameter | Insulation thickness | Sheath thickness | External diameter | Cable weight | Length | Drum |
(nxS+n1xS1+n2xS2mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (m) | (type) |
3x16+2x6+1x10 | 5,0 | 3,1 | 4,0 | 3,0 | 3,0 | 43,0 | 2700 | 500 | BD-16 |
3x25+2x10+1x10 | 6,2 | 4,0 | 4,0 | 3,0 | 3,5 | 48,0 | 4450 | 500 | BD-18 |
3x35+2x16+1x10 | 7,5 | 5,0 | 4,0 | 3,0 | 4,0 | 52,0 | 4100 | 500 | BD-18 |
3x50+2x16+1x10 | 8,9 | 5,0 | 4,0 | 3,0 | 4,0 | 55,0 | 4550 | 500 | BD-20 |
n1 - broj upravljačkih vodiča - number of control conductors
n2 - broj zaštitnih vodiča - number of protective conductors
S - presjek faznog vodiča - phase conductor cross-section
S1 - presjek upravljačkog vodiča - control conductor cross-section
S2 - presjek zaštitnog vodiča - protective conductor cross-section