Medium voltage rubber mining cables

HRN N.C5.364

VDE 0250/Teil 813

1-phase conductor: tinned copper fine-wired rope
2-semi-conductive layer: rubber compound at ethylene-propylene elastomere base (EPDM)
3-insulation: rubber compound at ethylene-propylene elastomere base (EPDM)
4-semi-conductive layer: semi conductive textile tape
5-inner sheath: EpN 64 - NR+SBR; EpN 65 - EPDM
6-electric protection: tinned copper wire concentrically around separator sheath
7-separator: polyester tape
8-separator sheath: rubber compound at ethylene-propylene elastomere base (EPDM), wrapped with semi conductive textile tape
9-control conductor: tinned copper wire concentrically around separator sheath
10-separator: polyester tape
11-external sheath: rubber compound at polychloroprene elastomere base (PCP)

Sheath colour: red
Flexible cable is intended for application in mines with methane pits. It is used under application of adequate cable controller of high voltage network, where application of armoured cables isnt possible because of site removal, and those are pit transformer stations for supplying of excavations and preparation sites. At laying and removal during operation, banding radius is at least 5D (D = external diameter).
nominal voltage: 3,6/6 kV
test voltage: 11 kV
standards: HRN N.C5.364; VDE 0250/Teil 813
Permissible conductor temperature: 90°C

SHEATH INSCRIPTION: EpN 65 3x25/16/4 mm2 3,6/6 kV ELKA HR year of production

*example: Designation of 3-core cable of 25mm2 cross-section of phase conductors with concentrical protective conductor of 16mm2 cross section over inner sheath made of semi-conductive rubber compound at EPDM base, with control conductor of 4mm2 cross-section between separator and external sheath

HRN: EpN 65 3x25/16/4 mm2

VDE: NTSCGEWÖU 3x25/16 KON+4ST KON
EpN 64, 65
Konstrukcija Promjer faznog vodiča Debljina izolacije Unutarnji plašt Separacijski plašt Vanjski plašt Vanjski promjer Težina kabela Dužina Bubanj
Construction Phase conductor diameter Insulation thickness Inner sheath Separating sheath External sheath External diameter Cable weight Length Drum
(*) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (m) (type)
3x16/10/4 5,0 3,0 2,0 1,5 3,5 49,0 2450 250 BD-16
3x25/16/4 6,2 3,0 2,0 1,5 3,5 52,0 3200 250 BD-16
3x35/16/4 7,5 3,0 2,0 1,5 3,5 55,0 3850 250 BD-16
3x16/25/4 5,0 3,0 2,0 1,5 3,5 49,0 2560 250 BD-16
3x25/25/4 6,2 3,0 2,0 1,5 3,5 52,0 3350 250 BD-16
3x35/25/6 7,5 3,0 2,0 1,5 3,5 55,0 3950 250 BD-18
(*)=nxS+n1xS1mm2
n - broj faznih vodiča - number of phase conductors
S - presjek faznog vodiča - phase conductor cross-section
S1 - broj zaštitnih vodiča - electric protection cross-section
S2 - presjek kontrolnog vodiča - control conductor cross-section