Armoured, fire-retardant, with electromagnetic compatibility (EMC) 0,6/1 kV
IEC 60092-350, IEC 60092-353
keyboard_arrow_downCable structure
1-conductor: tinned copper wire, class 2, IEC 60228 (50-300mm2 sector-shaped) see table
2-separator: on request
3-insulation: XLPE, acc. to IEC 600092-351
4-filler and inner covering: compound on polyolefin basis
5-armour: tinned copper wires braiding (min density 90% + wrapped copper-polyester tape, copper side in contact with braiding)
6-sheath: polyolefin, type SHF 1 acc. to IEC 60092-359 (SHF 2 on request)
Sheath Colour: black or grey
Insulation colours:
Single-core: black or gray
Two-cores: black, blue
Three-cores: black, blue, brown (or gr/ye)
Four-cores: black, blue, brown, white (or gr/ye)
Five-cores: black, black, blue, brown, white (or gr/ye) Seven-and multicore: white or black with numbers 1 ... n
SHEATH MARKER:
ELKA CS ATOX-MARIN BXOZO-HFTG EMC nxSmm 0,6/1 kV IEC 60092-353, IEC 60332-3A
2-separator: on request
3-insulation: XLPE, acc. to IEC 600092-351
4-filler and inner covering: compound on polyolefin basis
5-armour: tinned copper wires braiding (min density 90% + wrapped copper-polyester tape, copper side in contact with braiding)
6-sheath: polyolefin, type SHF 1 acc. to IEC 60092-359 (SHF 2 on request)
Sheath Colour: black or grey
Insulation colours:
Single-core: black or gray
Two-cores: black, blue
Three-cores: black, blue, brown (or gr/ye)
Four-cores: black, blue, brown, white (or gr/ye)
Five-cores: black, black, blue, brown, white (or gr/ye) Seven-and multicore: white or black with numbers 1 ... n
SHEATH MARKER:
ELKA CS ATOX-MARIN BXOZO-HFTG EMC nxSmm 0,6/1 kV IEC 60092-353, IEC 60332-3A
keyboard_arrow_downApplication
Connection of motors controlled through frequency converters.
keyboard_arrow_downTechnical data
nominal voltage: 0,6/1 kV
test voltage: 3,5 kV
standards:IEC 60092-350, IEC 60092-353
max working conductor temp: 90° C
inflamability test: IEC 60332-1, IEC 60332-3A test on corrosion: IEC 60754-1 smoke density test:IEC 61034 Sheath mark:
ELKA CS ATOX-MARIN BXOZO-HFTG EMC nxSmm 0,6/1 kV IEC 60092-353, IEC 60332-3A ELECTROMAGNETIC COMPATIBILITY PROPERTIES (EMC)
Frequency area: 0,1 up to 500 MHz
Impedance transfer: less than 100 mOhm/m
Screen attenuation: exceeding 60 dB
test voltage: 3,5 kV
standards:IEC 60092-350, IEC 60092-353
max working conductor temp: 90° C
inflamability test: IEC 60332-1, IEC 60332-3A test on corrosion: IEC 60754-1 smoke density test:IEC 61034 Sheath mark:
ELKA CS ATOX-MARIN BXOZO-HFTG EMC nxSmm 0,6/1 kV IEC 60092-353, IEC 60332-3A ELECTROMAGNETIC COMPATIBILITY PROPERTIES (EMC)
Frequency area: 0,1 up to 500 MHz
Impedance transfer: less than 100 mOhm/m
Screen attenuation: exceeding 60 dB
keyboard_arrow_downCross-sections (table)
BXOZO-HFTG EMC 0,6/1 kV
Konstrukcija | Debljina izolacije | Debljina plašta | Vanjski promjer | Min. radius savijanja | Težina kabela | Strujno opterećenje | |||
Construction | Insul. thickness | Sheath thickness | Extern.Diam. | Min. bending radius | Cable Weight | El. Resistance | |||
(nxmm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (A) | |||
3x35 | 0,9 | 1,7 | 28,5 | 190 | 1770 | 102 | |||
3x50 | 1,0 | 1,7 | 29,0 | 180 | 1970 | 126 | |||
3x70 | 1,1 | 1,9 | 32,0 | 190 | 2820 | 158 | |||
3x95 | 1,1 | 1,9 | 35,0 | 220 | 3610 | 193 | |||
3x120 | 1,2 | 2,1 | 39,0 | 240 | 4580 | 224 | |||
3x150 | 1,4 | 2,2 | 43,0 | 270 | 5810 | 256 | |||
4x6 | 0,7 | 1,3 | 18,5 | 100 | 650 | 34 | |||
4x16 | 0,7 | 1,5 | 22,5 | 140 | 1130 | 63 | |||
4x35 | 0,9 | 1,8 | 30,0 | 190 | 2200 | 102 |