Power cables with XLPE  insulation and PE  sheath with longitudinal water-resistant version of electrical protection

HRN HD 632

IEC 60480

1-conductor: Cu or Al compacted or segment rope, class 2
2-conductor screen: extruded semi-conductive XLPE
3-insulation: XLPE
4-insulation screen: extruded semi-conductive XLPE
5-separator: swelling tape, semi-conductive
6-metal screen: Cu wires and counter helix of copper tape
7-separator: swelling tape, semi-conductive
8-external sheath: black HDPE
The cable is intented for laying in earth, especially in wet grounds, canals, on brackets where no mechanical damages are expected and where the cable is not exposed to tensile strains.
nominal voltage: 64/110 kV
highest network voltage:123 kV
standards: IEC 60840; HRN HD 632
old mark: XHE 49, XHE 49-A
2XS(F)2Y
Cross section (n x mm2/mm2) Conductor diameter (mm) Insulation thickness (mm) Diameter over insulation (mm) Cable diameter (mm) Cable weight (kg/km) Minimal bending radius (m) Maximal force of dragging (kN)
1x150/95 14,1 18 54,9 64,5 4910 0,97 7,5
1x185/95 15,7 17 54,5 64,1 5145 0,96 9,2
1x240/95 18,0 16 54,8 64,4 5614 0,97 12,0
1x300/95 20,3 15 55,1 64,7 6085 1,00 15,0
1x400/95 23,0 15 57,6 67,4 7075 1,01 20,0
1x500/95 26,5 15 61,3 71,3 8185 1,07 25,0
1x630/95 30,3 15 64,5 74,8 9740 1,20 31,5
1x800/95 36,9 15 71,8 82,6 11869 1,24 40,0
A2XS(F)2Y
Cross section (n x mm2/mm2) Conductor diameter (mm) Insulation thickness (mm) Diameter over insulation (mm) Cable diameter (mm) Cable weight (kg/km) Minimal bending radius (m) Maximal force of dragging (kN)
1x150/95 14,1 18 54,9 64,5 3995 0,97 4,5
1x185/95 15,7 17 54,5 64,1 4026 0,96 5,5
1x240/95 18,0 16 54,8 64,4 4156 0,97 7,2
1x300/95 20,3 15 55,1 64,7 4263 1,00 9,0
1x400/95 23,0 15 57,6 67,4 4746 1,01 12,0
1x500/95 26,5 15 61,3 71,3 5287 1,07 15,0
1x630/95 30,3 15 64,5 74,8 5908 1,20 18,9
1x800/95 36,9 15 71,8 82,6 6925 1,24 24,0
1x1000/95 37,9 15 72,8 84,0 7409 1,26 30,0
1x1200/95 44,0 15 78,0 90,0 8010 1,35 36,0