Power cables with  XLPE insulation and PVC sheath, armoured with 2 steel tapes

IEC 60 502-1 (Cu/XLPE/STA/PVC, Al/XLPE/STA/PVC)

1-conductor: Cu rope (XP 41), Al rope (XP 41-A)
2-insulation: XLPE compound
3-filling: extruded elastomer or plastomer compound or wrapped thermoplastic tapes
4-armour: two (2) steel tapes
5-sheath: PVC compound
In earth, ducts, on support brackets, in dry and wet conditions etc, where one can expect mechanical damages and cables are not exposed to increased mechanical tensile strain.
In urban networks, industrial plants, electric power plants and other electricity consumers for elevated electricity and thermic strains (operating temperature of the conductor up to 90°C.
For the necessity of MTK control systems in distribution networks, at four-core cables of larger cross-section, an additional insulated conductor of 2.5mm2is applied in the middle among the cable cores.
nominal voltage:1 kV
test voltage: 3,5 kV
standards: IEC 60 502-1
XP 41, XP 41-A
Cross Section Insul. Thickness Sheath Thickness Overall Diam. Weight XP 41 Weight XP 41-A Length Drum
(n x mm2) (mm) (mm) (mm) (kg/km) (kg/km) (m) (type)
2x16 0,7 1,8 20,7 940 740 1000 BD-12
2x25 0,9 1,8 25,5 1635 1325 1000 BD-16
2x35 0,9 1,9 27,9 1975 1545 1000 BD-16
3x16 0,7 1,8 23,2 1400 1095 1000 BD-14
3x25 0,9 1,8 26,7 1915 1445 1000 BD-16
3x35 0,9 1,9 29,3 2340 1670 1000 BD-16
4x16 0,7 1,8 24,9 1590 1185 1000 BD-14
4x25 0,9 1,9 29,0 2290 1665 1000 BD-16
4x35 0,9 2,0 31,9 2835 1975 500 BD-14
4x50 1,0 2,1 36,3 3555 2365 500 BD-14
4x70 1,1 2,2 40,5 4615 2870 500 BD-16
4x95 1,1 2,4 46,2 6260 3950 500 BD-18
4x120 1,2 2,5 49,1 7500 4570 500 BD-20
4x150 1,4 2,7 55,6 8985 5415 500 BD-20
4x185 1,6 3,0 61,06 11780 7260 500 BD-20
4x240 1,7 3,0 64,8 13940 8100 500 BD-22
4x300 1,8 3,2 70,2 17185 9570 500 BD-22